Product images are provided for visual reference. Please confirm the final configuration and specifications with our team.
Industrial Testing Equipment
GROADA-AC415V-600KW-R of generator resistance load bank
Explore product details and technical information, or send us your requirements for application guidance and a quotation.
Request Product Information
Tell us what you need. Our team can follow up with product details and quotation information.
Product Overview & Technical Specifications
| Model | AC220V-6KW-R | AC380V-30KW-R | AC380V-60KW-R | AC380V-100KW-R | AC380V-200KW-R | AC380V-400KW-R | AC380V-500KW-R | AC380V-1000KW-R |
| Rated power | 0-6KW | 0-30KW | 0-60KW | 0-100KW | 0-200KW | 0-400KW | 0-500KW | 0-1000KW |
| Size (width * depth * height mm) | 480*600*277 | 500*750*1000 | 600*850*1000 | 600*850*1400 | 700*1000*1650 | 1100*1400*1700 | 1100*1400*1800 | 1500*1800*2000 |
| Weight | 25KG | 80KG | 130KG | 180KG | 250KG | 550KG | 650KG | 1100KG |
| Input current | 0-30A | 0-45A | 0-90A | 0-150A | 0-300A | 0-600A | 0-750A | 0-1500A |
| Minimum loading | 100W | 100W | 500W | 1KW | 1KW | 5KW | 10KW | 50KW |
| Other minimum loading power can be customized according to requirements | ||||||||
| Input voltage | AC220/230V | AC380/400V | ||||||
| Other input voltage can be customized according to requirements | ||||||||
| Power | PF=1.0 | |||||||
| Overall accuracy | 3% (other accuracy requirements can be customized according to requirements) | |||||||
| Control mode | Local manual/remote host computer (local manual control mode: circuit breaker/button/touch screen three-way optional, other methods can be customized as required) | |||||||
| Remote Interface | RS232/RS485/USB/RJ45/CAN/GPIB (other interface modes can be customized according to requirements) | |||||||
| Protection function | Emergency stop protection, over-temperature protection, fan load interlock protection, grounding protection (select over-voltage protection, over-current protection, short-circuit protection, fan overload, insufficient air volume) | |||||||
| Working power supply | AC220V | AC220V/380V | AC380V | |||||
| Display accuracy | 0.5 level (other explicit precision can be customized according to requirements | |||||||
| Display parameters | Voltage, current, power, frequency, power factor, etc. (other explicit methods can be customized according to requirements) | |||||||
| Cold sure way | Forward and out | Side air inlet and upper air outlet (other air outlet methods can be customized according to requirements) | ||||||
| Protection level | IP20 (other protection level can be customized according to requirements) | |||||||
| Appearance color | RAL7035 (other colors can be customized according to requirements) | |||||||
| Working temperature | -10 ℃ ~ 55 ℃ | |||||||
| Relative humidity | ≤95%RH | |||||||
| Altitude | ≤ 2500 m | |||||||
GROADA AC415V-600KW-R Resistive Load Bank: Comprehensive Power System Testing Solution
🔍 Product Overview
The GROADA AC415V-600KW-R Resistive Load Bank is engineered to simulate real-world electrical loads, providing a robust solution for testing and validating the performance of power systems. With a capacity of 600 kW at 415V AC, this load bank is ideal for applications requiring high power testing, ensuring that generators, uninterruptible power supplies (UPS), and other critical power infrastructure operate efficiently under full-rated loads.
⚙️ Key Features
-
High Power Capacity: Supports up to 600 kW at 415V AC, accommodating large-scale power systems.
-
Resistive Load Simulation: Emulates real-world operational conditions, providing accurate testing environments.
-
Continuous Operation: Designed for prolonged use, ensuring reliability during extended testing periods.
-
User-Friendly Interface: Equipped with intuitive controls for easy operation and monitoring.
-
Robust Construction: Built to withstand demanding environments, ensuring longevity and consistent performance.
🛠️ Applications
The AC415V-600KW-R Resistive Load Bank is versatile and suitable for various applications:
-
Generator Testing and Maintenance: Verifies that generators can handle full-rated loads, preventing potential failures during critical operations.
-
UPS Systems Validation: Ensures UPS systems provide uninterrupted power during outages by simulating real-world load conditions.
-
Power System Commissioning: Facilitates the commissioning of new power installations by simulating operational loads.
-
Routine Maintenance: Supports regular maintenance schedules to identify and rectify potential issues before they lead to system failures.
✅ Benefits
Utilizing the GROADA AC415V-600KW-R Resistive Load Bank offers several advantages:
-
Enhanced Reliability: Regular testing ensures power systems perform optimally, reducing the risk of unexpected failures.
-
Cost Savings: Identifying issues early through load testing can prevent costly repairs and downtime.
-
Compliance Assurance: Meets industry standards and regulations, ensuring compliance and safety.
-
Extended Equipment Lifespan: Regular load testing can prolong the life of power equipment by ensuring it operates within its designed parameters.
📈 Industry Insights
The global load bank market is experiencing significant growth, driven by increasing industrialization and the need for reliable power systems. According to industry reports, the market is projected to reach USD 412.9 million by 2032, growing at a CAGR of 4.5% from 2025 to 2032.
This growth underscores the importance of investing in high-quality testing equipment like the GROADA AC415V-600KW-R to ensure the reliability and efficiency of power systems across various industries.
📞 Contact Information
For more information or to request a quote, please contact:
-
Email: groada@163.com
-
Phone: +86-755-23339096
-
Address: Shenzhen, Guangdong, China