RLC负载组

GROADA-AC380V-30KW-RLC三相负载组

★★★★★
主要产品:
  • 交流负载组:R/RL/RLC/RCD
  • 直流负载组:DC5V-2000V,0A-5000A


模型AC220V-10KVA-RLCAC380V-30KVA-RLCAC380V-60KVA-RLCAC380V-100KVA-RLCAC380V-200KVA-RLCAC380V-300KVA-RLC
额定功率RLC=10KVARLC=30KVARLC=60KVARLC=100KVARLC=200KVARLC=300KVA
R=10KW;L=10KVA
C=10KVA
R=30KW;L=30KVA;
C=30KVA
R=60KW;L=60KVA;
C=60KVA
R=100KW;L=100KVA;
C=100KVA
R=200KW;L=200KVA;
C=200KVA
R=300KW;L=300KVA;
C=300KVA
其他电源可根据要求定制
尺寸(宽*深*高mm)500*750*1400600*850*15001000*1100*15001100*1600*15001500*1800*18002000*2000*2000
重量120公斤380公斤580公斤880公斤1500公斤2500公斤
输入电压交流220/230V交流380/400V
其他输入电压可根据要求定制
输入电流0-45A0-45A0-90A0-150A0-3:000-450A
最小载荷R=100W;L=100VA;
C=100VA
R=100W;L=100VA;
C=100VA
R=100W;L=100VA;
C=100VA
R=100W;L=100VA;
C=100VA
R=1KW;L=1KVA;
C=1KVA
R=1KW;L=1KVA;
C=1KVA
其他最小负载功率可根据要求定制
功率因数PF=0.1~1.0(其他功率因数可根据要求定制)
整体精度3%(其他精度要求可根据要求定制)
控制模式本地手动/远程主机(本地手动控制模式:断路器/按钮/触摸屏三路可选,其他方法可根据需要定制)
远程接口RS232/RS485/USB/RJ45/CAN/GPIB(其他接口模式可根据要求定制)
保护功能紧急停机保护、超温保护、风机负载联锁保护、接地保护(选择过压保护、过流保护、短路保护、风机超负荷、风量不足)
工作电源AC220V交流220V/380V交流380v
显示精度0.5级(其他显式精度可根据要求定制)
显示参数电压、电流、功率、频率、功率因数等。(其他显式方法可根据要求定制)
冷肯定的方式侧进风口和上出风口(其他出风口方式可根据要求定制)
保护级别IP20(其他防护等级可根据要求定制)
外观颜色RAL7035(其他颜色可根据要求定制)
工作温度-10 ℃ ~ 55 ℃
相对湿度≤95%相对湿度
高度≤2500米


GROADA-AC380V-30KW-RLC三相负载组——高精度RLC电源测试解决方案

GROADA-AC380V-30KW-RLC负载组是一种最先进的测试仪器,专为精确模拟现实世界的电气负载而设计。结合电阻性(R)、电感性(L)和电容性(C)该负载组使工程师和技术人员能够评估、验证和优化各种工业应用中的电力系统。无论您是测试发电机、UPS系统还是可再生能源装置,GROADA RLC Load Bank都能为性能验证和系统压力测试提供可靠、高精度的解决方案。


主要特点

  • 额定功率:30千瓦

  • 输入电压:交流380V,三相

  • 频率:50/60赫兹

  • 可调功率因数:0.1–1.0,支持滞后和领先负载

  • 加载步长分辨率:精细增量用于精确的负载模拟

  • 控制选项:本地面板和远程控制,操作灵活

  • 安全防护:过载、短路和超温报警


先进的技术优势

  1. 综合负载模拟
    电阻、电感和电容元件的集成使GROADA RLC负载组能够模拟几乎任何现实世界的负载条件。这种能力对于验证至关重要发电机性能、UPS稳定性和配电效率在不同的场景下。

  2. 高精度控制
    该设备具有可调节的负载步长,可确保精确的输出控制,偏差最小,使其成为精确负载复制至关重要的应用的理想选择。工程师可以准确地模拟部分或全部负载条件,以进行彻底的测试。

  3. 灵活的操作模式
    操作员可以在以下之间切换manual local control and remote automation, offering adaptability for on-site testing or integration into a larger automated testing system.

  4. Robust Safety Design
    Built-in protective features safeguard both the equipment and operators, allowing for safe and continuous operation even under high-load conditions.


跨行业应用

The GROADA-AC380V-30KW-RLC Load Bank is widely used in multiple sectors:

  • Power Generation and UPS Systems: Validates generators and uninterruptible power supplies by simulating full operational loads.

  • 数据中心: Ensures backup power systems perform reliably under real-world conditions.

  • 可再生能源设施: Tests wind, solar, and hybrid energy systems under fluctuating load scenarios to guarantee stability and efficiency.

  • Industrial and Commercial Facilities: Evaluates switchgear, transformers, and distribution networks to confirm operational capacity and safety.


Industry Insights & Market Trends

global load bank market is experiencing substantial growth due to the increasing reliance on reliable power infrastructure and the rise of renewable energy sources. Market analysis forecasts the industry will reach USD 524.1 million by 2032, growing at a CAGR of 6.2% from 2024 to 2032. Among load bank types, RLC load banks are projected to witness the fastest growth, driven by their versatility in simulating complex load conditions and supporting critical testing in power-sensitive industries.

This growth highlights the rising demand for precision testing equipment, making the GROADA RLC Load Bank an indispensable tool for modern power system validation.


Why Choose the GROADA-AC380V-30KW-RLC Load Bank?

  • Versatile Load Testing: Simulates resistive, inductive, and capacitive loads across a wide power factor range.

  • High Accuracy: Fine-tuned load increments allow precise emulation of real-world operating conditions.

  • Safe and Reliable: Comprehensive protective features ensure operator safety and equipment longevity.

  • Flexible Control Options: Supports local and remote operation for diverse testing environments.

  • Industry-Proven Quality: Built to meet stringent industry standards, offering long-term durability and reliable performance.


结论

GROADA-AC380V-30KW-RLC Three-Phase Load Bank is more than a testing device—it is a comprehensive solution for ensuring power system reliability, efficiency, and safety. By providing accurate load simulation, robust control, and versatile operation, it enables engineers to validate performance, prevent failures, and optimize system design.

For industries where reliable power is non-negotiable, the GROADA RLC Load Bank delivers unmatched precision, safety, and versatility, establishing itself as an essential tool for modern electrical testing and power management.

我们的产品